{"schema_version":"1.0","country":"us","country_name":"United States","topic":"grid-hosting-capacity","question":"Where can I get the available grid connection capacity per substation or node in the United States, for generation and for demand, with the latest value and its history?","territory":"us","territory_level":"country","parent_url":null,"published_on":"2026-11-19","research_reviewed_on":"2026-11-19","access_checked_on":"2026-11-19","answer":{"official_data":"partial","non_official_data":"none_found","summary":"No national US dataset of available connection capacity exists. Capacity is published utility by utility, mostly as ArcGIS services. Three were queried live: PG&E (GRIP: generation and load capacity in kW per line section, 2.09M sections), SCE (ICA per circuit segment, MAX_REMAIN_CAP per substation, available load capacity per circuit/substation for five plan years) and National Grid New York (PV hosting capacity per feeder and substation bank, no demand). CAISO's transmission heatmap shows substation headroom but offers no data download. No history was found in any service tested.","main_caveats":["Distribution values are indicative hosting capacity (ICA), not a guarantee of connection; PG&E and others state that all interconnections are subject to engineering review.","Level differs: PG&E gives line sections, SCE circuit segments plus substations, National Grid feeders and substation banks; only some of them give an identifiable substation value.","Only 3 of about 58 utilities/agencies listed in the DOE atlas (May 2024) were queried; transmission headroom exists only as CAISO's viewer, without data.","No service declares units: kW for PG&E and MW for National Grid are inferred from field names; SCE units are unknown (its user guide returned HTTP 403).","Queue and project layers (e.g. PG&E queued DG, GNA needs) are not available capacity and were excluded.","Services expose only the current snapshot plus per-record analysis dates; no archived series was found."],"confidence":"medium","confidence_reason":"Live queries worked for three utilities, but coverage is utility-specific, SCE units and SDG&E were not verified, and history was not found.","attributes":[{"attribute":"node","covered":"partial","source_ids":["pge-grip","sce-drpep","ng-ny"],"note":"PG&E EDSubstations (777) and line sections; SCE substations (735) and node_id; National Grid substation bank (t_node/t_ptid), 1,913 feeders.","gap":"not_published","gap_note":"Not every utility names substations; national coverage absent (3 utilities tested)."},{"attribute":"generation_capacity","covered":"partial","source_ids":["pge-grip","sce-drpep","ng-ny","caiso-poi"],"note":"PG&E GenCapacity_kW; SCE ica_overall_pv and MAX_REMAIN_CAP; NG feeder_min_hc/max_hc (PV); CAISO heatmap in MW (viewer).","gap":"not_published","gap_note":"Only utilities with a public map; calculation conditions differ and CAISO transmission values are not downloadable."},{"attribute":"demand_capacity","covered":"partial","source_ids":["pge-grip","sce-drpep"],"note":"PG&E LoadCapacity_kW per line section; SCE ica_overall_load and available load capacity (alc_year1-5) per circuit/substation.","gap":"not_published","gap_note":"National Grid NY layers tested give PV only; no transmission demand headroom found."},{"attribute":"latest_data","covered":"partial","source_ids":["pge-grip","sce-drpep","ng-ny"],"note":"PG&E layers edited 2026-10-29/2026-11-06, ICA dates up to Aug 2026; SCE load capacity 2026-11-19; NG hosting refresh 2026-03-31.","gap":"not_published","gap_note":"SCE ICA segments last edited 2025-09-17 (ICA table dated 2025-02-14); reference dates differ per record."},{"attribute":"historical_series","covered":"no","source_ids":[],"note":"Tested services expose only the current snapshot; per-record analysis dates show different vintages but not earlier values.","gap":"not_published","gap_note":"No archive or earlier values were found in the three services; Wayback copies or ArcGIS item versions were not checked."},{"attribute":"update_frequency","covered":"partial","source_ids":["caiso-poi","ng-ny","pge-grip"],"note":"CAISO states about 3 updates per year; NG shows hca_refresh 2026-03-31 and DG refresh 2026-10-02; PG&E ICA dates span monthly.","gap":"not_published","gap_note":"PG&E, SCE and National Grid state no schedule on the services; frequency is inferred from dates."}]},"sources":[{"source_id":"pge-grip","name":"PG&E Grid Resource Integration Portal (GRIP) - ICA line sections","publisher":"Pacific Gas and Electric Company","official":true,"landing_url":"https://www.pge.com/en/about/doing-business-with-pge/interconnections/distributed-resource-planning-data-and-maps.html","data_url":"https://services2.arcgis.com/mJaJSax0KPHoCNB6/ArcGIS/rest/services/DRPComplianceRelProd/FeatureServer/3","access":"api","format":"ArcGIS REST FeatureServer (JSON, GeoJSON, CSV via query)","license":"Unknown (PG&E data-portal disclaimer: no guarantees)","language":"English","has_coordinates":true,"location_precision":"exact","adds":"Generation and load integration capacity per line section (kW) with analysis date, plus substations and feeders; no auth.","first_seen_pass":1,"rank":1,"summary":"Open ArcGIS service with generation and load capacity in kW per line section, plus substations and feeders.","coverage_note":"PG&E territory only; 2.09M line sections, 777 substations.","data_date":"2026-10-29","caveats":["Line-section level, not substation.","Indicative, not a guarantee.","No history."],"coverage":{"geographic":"PG&E service territory, northern and central California."},"fine_print":{"unit":{"value":"kW per line section (LoadCapacity_kW, GenCapacity_kW).","attempts":[]},"inclusion_rule":{"value":"Line sections with ICA analysis; 796,358 of 2,088,904 have no ICA_Analysis_Date.","attempts":[]},"reference_date":{"value":"ICA_Analysis_Date per section (e.g. Jun 2026); layer last edit 2026-10-29","attempts":[]},"update_frequency":{"value":"Rolling; no stated schedule","attempts":[]},"exclusions":{"value":"Sections without ICA results (layer 'ICA Not Available').","attempts":[]}},"key_fields":[{"field":"FeederId/FeederName","meaning":"Feeder"},{"field":"CSV_LineSection","meaning":"Line section id"},{"field":"LoadCapacity_kW","meaning":"Available load capacity"},{"field":"GenCapacity_kW","meaning":"Available generation capacity"},{"field":"limiting_criteria","meaning":"Limiting factor"},{"field":"ICA_Analysis_Date","meaning":"Analysis month"}],"how_to_use":{"example_request":"curl -G 'https://services2.arcgis.com/mJaJSax0KPHoCNB6/ArcGIS/rest/services/DRPComplianceRelProd/FeatureServer/3/query' --data-urlencode 'where=FeederName IS NOT NULL' --data-urlencode 'outFields=FeederName,CSV_LineSection,LoadCapacity_kW,GenCapacity_kW,limiting_criteria,ICA_Analysis_Date' --data-urlencode 'resultRecordCount=3' --data-urlencode 'returnGeometry=false' --data-urlencode 'f=json'","example_result":"KING CITY 1106, section 3952502: load 50 kW, generation 0 kW, limited by Voltage, ICA Jun 2026.","steps":["Page with resultOffset (maxRecordCount 2000).","Join FeederId to layer 2 FeederDetail and Substation to layer 0 EDSubstations (777 substations).","Use returnCountOnly=true to size queries (2,088,904 sections)."],"reading_traps":["Capacity is per line section, not per substation; aggregate with care.","Value 0 may mean no capacity or a constrained section.","Layer 33 PendingLoad and layers 11/12 are needs and forecasts, not capacity."]},"test":{"tested_on":"2026-11-19","method":"api_query","http_status":200,"content_type":"application/json","size_bytes":null,"records_total":2088904,"records_for_country":2088904,"problems":["No metadata declares units; kW taken from field names.","No history found."]},"evidence":[{"claim":"PG&E is retiring the old ICA map; data are on GRIP.","url":"https://www.pge.com/en/about/doing-business-with-pge/interconnections/distributed-resource-planning-data-and-maps.html","quote":"PG&E is retiring the ICA map and the DIDF map. All data and functionality is available on the new Grid Resource Integration Portal"},{"claim":"Interconnections are subject to engineering review.","url":"https://www.pge.com/en/about/doing-business-with-pge/interconnections/distributed-resource-planning-data-and-maps.html","quote":"All interconnections are subject to engineering review."}],"members":[],"members_summary":null},{"source_id":"sce-drpep","name":"SCE Distributed Resources Plan External Portal (DRPEP) - ICA and available load capacity","publisher":"Southern California Edison","official":true,"landing_url":"https://drpep-sce2.opendata.arcgis.com/","data_url":"https://services5.arcgis.com/z6hI6KRjKHvhNO0r/arcgis/rest/services/ICA_Layer/FeatureServer","access":"api","format":"ArcGIS FeatureServer (JSON, CSV, GeoJSON, Shapefile via Hub)","license":"Unknown (not stated on layers)","language":"English","has_coordinates":true,"location_precision":"exact","adds":"ICA load and PV per circuit segment, maximum remaining capacity per substation, and available load capacity per circuit and substation for five plan years.","first_seen_pass":1,"rank":2,"summary":"ArcGIS Hub with ICA for load and PV per circuit segment, a substation remaining-capacity layer and available load capacity by plan year.","coverage_note":"SCE territory; 524,522 segments, 735 substations.","data_date":"2026-11-19","caveats":["Units not declared.","ICA layers dated 2025.","Indicative values."],"coverage":{"geographic":"SCE service territory, southern California."},"fine_print":{"unit":{"value":"Not declared in layer metadata; values appear to be MW (unverified).","attempts":[]},"inclusion_rule":{"value":"Circuit segments (524,522), substations (735), circuit and substation ALC rows (48,350).","attempts":[]},"reference_date":{"value":"ICA tables FGDB_DATE 02-14-2025; ICA segments edited 2025-09-17; ALC updated 2026-11-19","attempts":[]},"update_frequency":{"value":"Not stated","attempts":[]},"exclusions":{"value":"Non-3-phase segments in a separate layer.","attempts":[]}},"key_fields":[{"field":"ica_overall_load","meaning":"ICA for load on the section"},{"field":"ica_overall_pv","meaning":"ICA for PV"},{"field":"uniform_generation","meaning":"Uniform generation ICA"},{"field":"MAX_REMAIN_CAP","meaning":"Substation maximum remaining capacity"},{"field":"alc_year1..5","meaning":"Available load capacity by plan year"},{"field":"subst_capacity_y1..5","meaning":"Substation capacity"}],"how_to_use":{"example_request":"curl -G 'https://services5.arcgis.com/z6hI6KRjKHvhNO0r/arcgis/rest/services/ICA_Layer/FeatureServer/0/query' --data-urlencode 'where=1=1' --data-urlencode 'outFields=SUBST_ID,SUB_NAME,MAX_REMAIN_CAP,TOTAL_GEN,QUEUED_GEN' --data-urlencode 'resultRecordCount=2' --data-urlencode 'returnGeometry=false' --data-urlencode 'f=json'","example_result":"Windsor Hills (SUBST_ID 505): MAX_REMAIN_CAP 10.68, TOTAL_GEN 2.818, QUEUED_GEN 0.276; Tamarisk/Agave section 207621115: ica_overall_load 2.14, ica_overall_pv 4.","steps":["Use ICA_Layer layers 0 (substations), 2 (circuit segments).","Use AVL_LOAD_CAP_TOGGLE layer 1 for load capacity by circuit/substation and plan year."],"reading_traps":["Units are not declared in the service; values must be read with the DERiM user guide.","Notes flag constrained circuits where load was aggregated.","The DCAT feed lists modified dates of 2025 for most layers."]},"test":{"tested_on":"2026-11-19","method":"api_query","http_status":200,"content_type":"application/json","size_bytes":null,"records_total":524522,"records_for_country":524522,"problems":["SCE DERiM user guide URL returned HTTP 403, so units and method were not verified.","Layer dates for ICA are 2025; verify freshness."]},"evidence":[{"claim":"Hub catalogue lists the ICA layers and available load capacity layers.","url":"https://drpep-sce2.opendata.arcgis.com/api/feed/dcat-us/1.1.json","quote":"ICA - Circuit Segments; AVL LOAD CAP FULL AND PARTIAL SUBMITTAL"}],"members":[],"members_summary":null},{"source_id":"ng-ny","name":"National Grid New York System Data Portal - Hosting Capacity Data","publisher":"National Grid (New York)","official":true,"landing_url":"https://systemdataportal.nationalgrid.com/","data_url":"https://systemdataportal.nationalgrid.com/arcgis/rest/services/NYSDP/Hosting_Capacity_Data/MapServer","access":"api","format":"ArcGIS MapServer REST (JSON)","license":"Unknown","language":"English","has_coordinates":true,"location_precision":"exact","adds":"PV hosting capacity per feeder (min/max, MW) and substation-bank data linked to NYISO nodes; includes installed and queued DG.","first_seen_pass":1,"rank":3,"summary":"ArcGIS REST service of PV hosting capacity per feeder and substation bank with NYISO node ids.","coverage_note":"National Grid NY, 1,913 feeders; hosting analysis 2026-03-31.","data_date":"2026-03-31","caveats":["PV only.","Units inferred.","No history."],"coverage":{"geographic":"National Grid upstate and Long Island operating companies in New York; 1,913 feeders."},"fine_print":{"unit":{"value":"MW (feeder_max_hc, feeder_min_hc) - unit inferred from field names.","attempts":[]},"inclusion_rule":{"value":"Feeders and substation banks with HCA results.","attempts":[]},"reference_date":{"value":"hca_refresh_date 2026-03-31; DG refresh 2026-10-02","attempts":[]},"update_frequency":{"value":"Not stated","attempts":[]},"exclusions":{"value":"Load hosting capacity not in these layers.","attempts":[]}},"key_fields":[{"field":"Master_CDF","meaning":"Feeder id"},{"field":"substation_bank_name","meaning":"Substation bank"},{"field":"feeder_max_hc/feeder_min_hc","meaning":"PV hosting capacity"},{"field":"substation_bank_thermal_capacity","meaning":"Bank rating"},{"field":"t_node/t_ptid","meaning":"NYISO node"}],"how_to_use":{"example_request":"curl -G 'https://systemdataportal.nationalgrid.com/arcgis/rest/services/NYSDP/Hosting_Capacity_Data/MapServer/0/query' --data-urlencode 'where=1=1' --data-urlencode 'outFields=Master_CDF,substation_bank_name,feeder_max_hc,feeder_min_hc,hca_refresh_date' --data-urlencode 'resultRecordCount=2' --data-urlencode 'returnGeometry=false' --data-urlencode 'f=json'","example_result":"Feeder 36_30_32752 (McKOWNVILLE TB 2): max 8.85, min 0.9; installed DG 0.07; hca_refresh 2026-03-31; bank thermal capacity 23.8, node NEWKRMKL_115KV_TB1.","steps":["Layer 0 = feeders, layer 1 = substation banks (1,913 each), layer 2 = primary-level points (452,342).","Dates are epoch milliseconds."],"reading_traps":["Generation (PV) only.","Layers 0 and 1 both returned 1,913 rows; confirm whether they are one-to-one."]},"test":{"tested_on":"2026-11-19","method":"api_query","http_status":200,"content_type":"application/json","size_bytes":null,"records_total":1913,"records_for_country":1913,"problems":["No unit or method metadata on the service."]},"evidence":[],"members":[],"members_summary":null},{"source_id":"caiso-poi","name":"CAISO Points of Interconnection Heatmap","publisher":"California ISO","official":true,"landing_url":"https://www.caiso.com/generation-transmission/generator-interconnection","data_url":"https://www.caiso.com/documents/points-of-interconnection-heatmap-frequently-asked-questions.pdf","access":"web_viewer_only","format":"Web map; FAQ PDF","license":"Unknown","language":"English","has_coordinates":null,"location_precision":null,"adds":"Transmission-level available injection capacity by ISO-controlled substation, shown on a map after FERC Order 2023.","first_seen_pass":1,"rank":4,"summary":"Only transmission-level source found; viewer with substation headroom, no data download.","coverage_note":"ISO-controlled substations; refreshed about 3 times a year.","data_date":null,"caveats":["Viewer only.","Map not opened.","Indicative; not a queue slot."],"coverage":{"geographic":"CAISO-controlled substations."},"fine_print":{"unit":{"value":"MW (per the FAQ and search summary).","attempts":[]},"inclusion_rule":{"value":"ISO-controlled substations only.","attempts":[]},"reference_date":{"value":"Updated within 30 days of each cluster study","attempts":[]},"update_frequency":{"value":"About 3 times a year (stated)","attempts":[]},"exclusions":{"value":"Substations not under ISO control.","attempts":[]}},"key_fields":[],"how_to_use":{"example_request":"Not reproducible: the FAQ says GIS and source data cannot be provided.","example_result":"FAQ PDF retrieved (130,165 bytes); map not opened.","steps":["Use the interactive map; no download."],"reading_traps":["Based on transfer limits and P1 contingency only; different from the Constraint Mapping spreadsheet."]},"test":{"tested_on":"2026-11-19","method":"page_only","http_status":200,"content_type":"application/pdf","size_bytes":130165,"records_total":null,"records_for_country":null,"problems":["The heatmap page URL tried returned 404; only the FAQ was read.","Data are not downloadable per the FAQ."]},"evidence":[{"claim":"CAISO cannot provide the backend GIS data.","url":"https://www.caiso.com/documents/points-of-interconnection-heatmap-frequently-asked-questions.pdf","quote":"Unfortunately, we are unable to provide the source data, which include the GIS datasets."},{"claim":"Updated roughly three times a year.","url":"https://www.caiso.com/documents/points-of-interconnection-heatmap-frequently-asked-questions.pdf","quote":"the Heatmap will be updated roughly 3 times a year"}],"members":[],"members_summary":null},{"source_id":"us-atlas","name":"U.S. Atlas of Electric Distribution System Hosting Capacity Maps","publisher":"U.S. Department of Energy","official":true,"landing_url":"https://www.energy.gov/eere/us-atlas-electric-distribution-system-hosting-capacity-maps","data_url":null,"access":"web_viewer_only","format":"HTML table","license":"Public domain (US government)","language":"English","has_coordinates":null,"location_precision":null,"adds":"Index of utilities and agencies that publish hosting capacity maps; a pointer to further utilities.","first_seen_pass":1,"rank":5,"summary":"DOE index of 58 utility and agency hosting-capacity maps; a pointer, not a dataset.","coverage_note":"As of May 2024; only 3 members verified here.","data_date":"2024-05-31","caveats":["Index only.","Table not parsed.","May 2024 date."],"coverage":{"geographic":"58 utilities and state agencies in 26 states, DC and Puerto Rico as of May 2024 (per page)."},"fine_print":{"unit":null,"inclusion_rule":{"value":"Public maps only.","attempts":[]},"reference_date":{"value":"May 2024","attempts":[]},"update_frequency":null,"exclusions":{"value":"Utilities without public maps.","attempts":[]}},"key_fields":[],"how_to_use":{"example_request":"Open the Atlas page and follow each utility link.","example_result":"Page loaded (HTTP 200); its table of utilities was not parsed.","steps":["Pick utility; test its ArcGIS endpoint."],"reading_traps":["The Atlas is a list of maps, not a dataset; it does not host capacity values."]},"test":{"tested_on":"2026-11-19","method":"page_only","http_status":200,"content_type":"text/html","size_bytes":136061,"records_total":null,"records_for_country":null,"problems":["Atlas table not parsed; only five members tested."]},"evidence":[{"claim":"As of May 2024, 58 utilities and state agencies had published maps.","url":"https://www.energy.gov/eere/us-atlas-electric-distribution-system-hosting-capacity-maps","quote":"As of May 2024, 58 utilities and state agencies have published maps in 26 states, Washington, D.C., and Puerto Rico."}],"members":[{"name":"PG&E GRIP","landing_url":"https://www.pge.com/en/about/doing-business-with-pge/interconnections/distributed-resource-planning-data-and-maps.html","data_url":"https://services2.arcgis.com/mJaJSax0KPHoCNB6/ArcGIS/rest/services/DRPComplianceRelProd/FeatureServer","access":"api","tested":true,"data_found":true,"note":"Line-section load and generation capacity (kW)."},{"name":"SCE DRPEP","landing_url":"https://drpep-sce2.opendata.arcgis.com/","data_url":"https://services5.arcgis.com/z6hI6KRjKHvhNO0r/arcgis/rest/services/ICA_Layer/FeatureServer","access":"api","tested":true,"data_found":true,"note":"ICA segments, substations, available load capacity."},{"name":"National Grid New York","landing_url":"https://systemdataportal.nationalgrid.com/","data_url":"https://systemdataportal.nationalgrid.com/arcgis/rest/services/NYSDP/Hosting_Capacity_Data/MapServer","access":"api","tested":true,"data_found":true,"note":"PV hosting capacity per feeder."},{"name":"SDG&E ICA","landing_url":"https://sdge.com/node/7111","data_url":null,"tested":true,"data_found":null,"note":"RAM map page found in search; ICA user guide returned HTTP 403; no data endpoint reached."},{"name":"Con Edison","landing_url":"https://www.coned.com/en/business-partners/hosting-capacity","data_url":null,"tested":false,"data_found":null,"note":"Mentioned by a search result; not opened."}],"members_summary":{"total":58,"listed":5,"tested":4,"data_found":3,"scope_note":"Universe: 58 utilities and agencies per the DOE Atlas (May 2024). Five were listed here; three returned live capacity data, one was blocked and one was not tested.","pattern":"Most publish ArcGIS map or feature services."},"member_scope":{"total":58,"note":"Universe: 58 utilities and agencies per the DOE Atlas (May 2024). Five were listed here; three returned live capacity data, one was blocked and one was not tested.","pattern":"Most publish ArcGIS map or feature services."}}],"sector":{"regulator":{"name":"California Public Utilities Commission (ICA mandates); state regulators elsewhere; FERC for transmission","url":"https://www.cpuc.ca.gov/industries-and-topics/electrical-energy/infrastructure/distribution-planning/data-portals-and-integration-capacity-analysis"},"operators":{"structure":"Thousands of utilities and several ISOs/RTOs; no national publisher.","note":"Only a minority publish maps (DOE atlas: 58 of about 2,000 utilities).","census_url":"https://www.energy.gov/eere/us-atlas-electric-distribution-system-hosting-capacity-maps"},"publication_obligation":{"exists":"yes","norm":"CPUC D.24-10-030 ordered improvements to IOU data portals and ICA (California only)","url":"https://www.cpuc.ca.gov/industries-and-topics/electrical-energy/infrastructure/distribution-planning/data-portals-and-integration-capacity-analysis","what_must_be_published":"ICA maps and data portals for PG&E, SCE, SDG&E","frequency":"Not verified"},"consolidated_republication":{"found":false,"note":"DOE Atlas indexes links but does not republish values.","checked_pages":[{"organization":"DOE","url":"https://www.energy.gov/eere/us-atlas-electric-distribution-system-hosting-capacity-maps","saw":"Index of 58 maps as of May 2024."}]}},"national_registry":{"exists":"no","note":"No national register of connection capacity found; DOE Atlas is an index of map links.","checked_pages":[{"organization":"DOE","url":"https://www.energy.gov/eere/us-atlas-electric-distribution-system-hosting-capacity-maps","saw":"58 utilities/agencies with public maps (May 2024)."}]},"if_unstructured":{"summary":null,"recipe":[],"where_published":[]},"related_not_answering":[{"name":"PG&E GNA and DER forecast layers","url":"https://services2.arcgis.com/mJaJSax0KPHoCNB6/ArcGIS/rest/services/DRPComplianceRelProd/FeatureServer","why":"Grid needs and forecasts, not available capacity."},{"name":"Interconnection queues (ISO/RTO)","url":"https://www.caiso.com/generation-transmission/generator-interconnection","why":"Queues list requests, not available capacity."}],"open_questions":["Pending: SDG&E ICA (Load and Generation) endpoints. Start: https://sdge.com/node/7111 and CPUC data portal page; the user guide returned 403.","Pending: SCE units and method from the DERiM user guide (HTTP 403 from csrpqa host). Start: SCE DRPEP Hub item pages.","Pending: Con Edison, Xcel Energy, ComEd, Duke, Eversource, and VELCO maps; load capacity layers for NY (Joint Utilities). Start: DOE Atlas table.","Pending: transmission headroom beyond CAISO (ISO-NE, PJM, ERCOT, MISO, SPP). Start: ISO-NE heatmap page; no source tested.","Pending: history of ICA values (archived FeatureServer snapshots, CPUC filings, Wayback). Start: PG&E GRIP item page."],"history":[{"pass":1,"date":"2026-11-19","role":"research","model":"claude-sonnet-5-5 (Sonnet 5.5)","rules_version":"us-energia-industria-2026-11-19","note":"Queried PG&E, SCE and National Grid NY ArcGIS services live; read CAISO heatmap FAQ; DOE Atlas page opened but not parsed. SDG&E/SCE PDFs blocked (403). Effort level not exposed; user launched as Sonnet High.","headline":{"official_data":"partial","non_official_data":"none_found"},"sources":{"total":5,"new":5,"dropped":0},"negatives":{},"effort":{"pages":22,"minutes":45}}],"local_terms":[{"term":"ICA","language":"English","meaning":"Integration Capacity Analysis: California utilities' hosting-capacity method."},{"term":"Hosting capacity","language":"English","meaning":"Indicative distribution capacity available for new generation or load."},{"term":"Feeder / line section","language":"English","meaning":"Distribution circuit and its segments, the unit of PG&E and SCE ICA."}],"provenance":{"pass_count":1,"models":["claude-sonnet-5-5 (Sonnet 5.5)"],"minutes_estimate":45,"pages_opened":22,"passes":[{"pass":1,"date":"2026-11-19","model":"claude-sonnet-5-5 (Sonnet 5.5)"}],"note":"Minutes are researcher estimates. Counts describe documented passes, not publication approval. Missing history or effort is not reconstructed."},"card_url":"https://georutter.org/v1/us/grid-hosting-capacity.json","detail_url":"https://georutter.org/v1/us/grid-hosting-capacity/detail.json","html_url":"https://georutter.org/us/grid-hosting-capacity/","country_url":"https://georutter.org/v1/countries/us.json"}